- Home
- Products
- CPS-M1-060
CPS-M1-060
Smart and innovative: the pre-configured CPS-M1-060 SHEV control panel is faster than the fire brigade. A load current of 60 A, up to four combined RT and RM lines and ten independently controllable motor connections herald a new dimension in safety technology.
Features
- Power supply to connected drives with a total current draw of up to 60 A
- Tested and certified to ISO 21927-9, VdS 2581, VdS 2593 and DIN EN 12101-10.
- The AdComNet bus system for seamless interconnection of modules within the CPS-M and other D+H AdComNet components.
- Two-way communication with ACB-compatible drives
- Power supply and communication connection via integrated connectors
- Customisable, programmable control panel functions
- Elegant menu control via a 3.5" colour touch panel, through which the system status of individual modules can be visually monitored (optional)
- Freely assignable lines/groups
- Trigger module TMA: 2 independent lines for connecting up to 10 SHEV control panels each and 30 fire detectors
- Trigger module AM: 2 independent groups for connecting drives, each with a total maximum current of 10 A
Gallery
Technical data
| CPS-M1-060 | |
|---|---|
| Power supply | 230 V AC / 50 Hz / 1570 VA |
| Output | 24 V DC / 60 A |
| Ripple | < 50 mVss |
| Battery | Type 5 (2x) / Type 6 (2x) |
| Number of groups | default 6, max. 10* |
| Number of lines | default 2, max. 4* |
| Monitoring mode | pulse operation |
| Operating mode SHEV / daily ventilation | short-term operation 30% duty cycle |
| Protection rating | IP 54 |
| Temperature range | -5 °C ... +40 °C |
| Material | Steel |
| Colour | Light grey (~ RAL 7035) |
| W x H x D | 600 x 800 x 260 mm |
| Weight | ≥ 26.20kg ** |
** Depending on the number of groups and lines selected.
Certificates and approvals
- VdS Schadenverhütung
Need more information?
Contact our sales team by phone at +420 312 672 903 or by e-mail at [email protected].