Product catalogue
  • 3
    3

    Fire curtains separate fire compartments, slowing the spread of fire in a warehouse, production hall, shopping centre or car park for 15 to 120 minutes.

  • FK servis - Smoke barriers
    FK servis - Smoke barriers

    Smoke barriers divide a space into several smaller smoke zones. These are then easier to ventilate using a smoke and heat exhaust ventilation system.

  • Smoke and heat exhaust ventilation
    Smoke and heat exhaust ventilation

    Smoke and heat exhaust ventilation minimises property damage, makes it easier for firefighters to intervene and gives people enough time to leave the building safely.

  • Louvre windows and rooflights
    Louvre windows and rooflights

    Louvre windows certified to standard 12101-2, not just for smoke and heat exhaust ventilation systems, but also for smoke and heat exhaust ventilation of protected escape routes.

  • Electromobility
    Electromobility

    Systems and equipment for limiting the spread of electric vehicle fires, especially in public and private multi-storey car parks.

  • Daily ventilation 1
    Daily ventilation 1

    Natural ventilation systems ensure a steady flow of fresh air, removing heat and moisture. Even fully automatically.

FK ROLL EI

INSULATING FIRE CURTAINS
Category:

They have EI fire resistance, which prevents heat transfer for 15 to 120 minutes. They meet stricter criteria than FK ROLL EW, which is why they are suitable for, for example, separating escape routes. All FK ROLL EI variants have built-in water spraying that is not visible and has a false-alarm safeguard.

Until there is a fire, the curtains are almost invisible. Compared to other fire shutters, FK ROLL textile fire curtains are lighter, smaller and blend into the interior better. We manufacture them only from proven components from Germany.

FK ROLL EW Blue
FK ROLL EW extended Blue
FK ROLL EW White
FK ROLL EW Black

6 reasons to choose FK ROLL EI

Hydrant water misting built directly into the casing
Hydrant water misting built directly into the casing

Hydrant water spraying built directly into the headbox

FK ROLL EI does not need external cooling, which does not work as well and looks worse. It is protected by a false-alarm safeguard that prevents flooding and damage to the building.

Protection against power failure
Protection against power failure

Protection against power failure

In the event of an unwanted power failure, the curtain stays up so that it does not obstruct operations in the building. The system is battery-powered, which ensures correct operation in a fire.

We develop, manufacture and install fire curtains ourselves
We develop, manufacture and install fire curtains ourselves

We develop, manufacture and install fire curtains ourselves

We constantly innovate and improve our curtains to provide maximum protection. Installation is carried out throughout the Czech Republic and Slovakia by our team of experienced technicians.

We will incorporate fire curtains into your fire safety system
We will incorporate fire curtains into your fire safety system

We will incorporate fire curtains into your fire safety system

In a way that meets all standards. We will prepare a solution tailored exactly to the needs of your building.

Long-term and honest service of fire curtains
Long-term and honest service of fire curtains

Long-term, honest fire curtain servicing

We pride ourselves on fairness. We do not sell curtains below cost only to then charge you excessively high fees for annual function checks.

EI curtains meet Czech standards and hold all the necessary certificates
EI curtains meet Czech standards and hold all the necessary certificates

EI curtains meet Czech standards and hold all the necessary certificates

FK ROLL EI fire shutters have passed strict tests and can therefore be used throughout the Czech Republic and Slovakia.

3 ways to anchor fire curtains

Installation into a structural opening

FK servis | FK ROLL EI - anchoring method into the opening
FK servis | FK ROLL EI - anchoring method into the opening
  • We fit the curtain directly into the opening, for example into a passage between two sections of a hall.
  • This reduces the clear dimensions of the opening by 200 mm on the horizontal axis and by 200 to 270 mm on the vertical axis – depending on the overall dimensions of the specific shutter.
  • The roller shutter can be clad in plasterboard and is almost invisible.

Anchoring the curtain in front of the structural opening

FK servis | FK ROLL EI - anchoring method onto the opening
FK servis | FK ROLL EI - anchoring method onto the opening
  • Using a steel structure, we fix the curtain to the lintel above the structural opening.
  • This means we do not reduce the clear dimensions of the structural opening. The raised structure is protected against damage, for example from a forklift, and is easily accessible, which makes maintenance easier.

Installation into the ceiling

FK servis | FK ROLL EI - anchoring method into the ceiling
FK servis | FK ROLL EI - anchoring method into the ceiling
  • We anchor the curtain to the ceiling so that there is no reduction in the clear height of the opening.
  • So that the curtain is not visible, we install its headbox flush with the suspended ceiling.
  • This is useful, for example, in shopping centres or office buildings, where the fire shutter must not disrupt the appearance of the space.

Technical data

FK ROLL EI
Fire resistance EI 15, EI 30, EI 45, EI 60, EI 90, EI 120
Material Fabric made of glass and anti-corrosion fibres
Fabric weight 740 g/m2
Fabric colour grey-silver
Power supply 230 V AC
Drive 24 V DC
Side guide dimensions 120 × 60 mm
Headbox dimensions 200x200 to 250x250 mm*
Colour of visible parts Any shade to the RAL palette
* Depending on the final dimensions.

We will prepare a quote for you and answer all your questions

Leave us your contact details. We will get back to you shortly.